ALL PLCs

  1. #41
    عضو فعال جداً

    User Info Menu

    اقتباس المشاركة الأصلية كتبت بواسطة مهندس/اسماعيل مشاهدة المشاركة
    السلام عليكم
    ممكن معلومات عن plc ماركه LG
    http://www.lgis.com/product/product/...in.asp#A02;001

    اليك هذا الرابط


    0 Not allowed!

  2. #42
    جديد

    User Info Menu

    To Eng SAAD RASHED

    thanks alot for your help
    Dear sir,
    I have the Attached Network and it was Working Good , But Suddenly the Hard Disk of PC was Damaged and i forced to install the windows , RSlinx , Rslogix500 and Rsview runtime again
    But when i tried to make Communication with the Network using RSlinx on PC
    I Have No Response from the CPU , and i return the CPU of SLC5/03 PLC to initial Factory Setting by Jumber (VBB , GND ) terminals and downloaded the Rslogix 500 user program again ,But when i tried to make communication again with the system using Rslinx with the following configurtion:
    Driver Type: RS-232 DF1 Device
    Device: SLC-CH0 / micro / panel view
    comm port : com1
    baud rate: 19200
    parity: None
    Stop Bits: 1
    Protocol : Full Duplex
    Error Checking: CRC
    the communication is passed for only SLC5/03 and i can't communicate with micrologix1000.
    Notes :
    ALL the Devices is Powered UP
    My Questions are:
    1- Why this bad communication happened ?and how i overcome this problem?
    2-What the right configuration of the Rslinx that i can communicte with all Devices
    (micrologix1000 and SLC 5/03)



    الصور المرفقة الصور المرفقة

    0 Not allowed!

  3. #43
    عضو

    User Info Menu

    شكرا يا باشا


    0 Not allowed!

  4. #44

  5. #45
    جديد

    User Info Menu

    الى المهندس Saad Rashed

    انا كان لى سؤال وكنت محتاج مساعدتك فى الاجابة عليه
    ارجو الرد


    0 Not allowed!

  6. #46

  7. #47
    جديد

    User Info Menu

    Have you had answer to my question? yes or No, this is third queary

    :confused:
    اقتباس المشاركة الأصلية كتبت بواسطة hatemeid مشاهدة المشاركة
    thanks alot for your help

    Dear sir,
    I have the Attached Network and it was Working Good , But Suddenly the Hard Disk of PC was Damaged and i forced to install the windows , RSlinx , Rslogix500 and Rsview runtime again
    But when i tried to make Communication with the Network using RSlinx on PC
    I Have No Response from the CPU , and i return the CPU of SLC5/03 PLC to initial Factory Setting by Jumber (VBB , GND ) terminals and downloaded the Rslogix 500 user program again ,But when i tried to make communication again with the system using Rslinx with the following configurtion:
    Driver Type: RS-232 DF1 Device
    Device: SLC-CH0 / micro / panel view
    comm port : com1
    baud rate: 19200
    parity: None
    Stop Bits: 1
    Protocol : Full Duplex
    Error Checking: CRC
    the communication is passed for only SLC5/03 and i can't communicate with micrologix1000.
    Notes :
    ALL the Devices is Powered UP
    My Questions are:
    1- Why this bad communication happened ?and how i overcome this problem?
    2-What the right configuration of the Rslinx that i can communicte with all Devices
    (micrologix1000 and SLC 5/03)



    0 Not allowed!

  8. #48

  9. #49

  10. #50
    عضو فعال جداً

    User Info Menu

    اقتباس المشاركة الأصلية كتبت بواسطة hatemeid مشاهدة المشاركة
    thanks alot for your help
    Dear sir,
    I have the Attached Network and it was Working Good , But Suddenly the Hard Disk of PC was Damaged and i forced to install the windows , RSlinx , Rslogix500 and Rsview runtime again
    But when i tried to make Communication with the Network using RSlinx on PC
    I Have No Response from the CPU , and i return the CPU of SLC5/03 PLC to initial Factory Setting by Jumber (VBB , GND ) terminals and downloaded the Rslogix 500 user program again ,But when i tried to make communication again with the system using Rslinx with the following configurtion:
    Driver Type: RS-232 DF1 Device
    Device: SLC-CH0 / micro / panel view
    comm port : com1
    baud rate: 19200
    parity: None
    Stop Bits: 1
    Protocol : Full Duplex
    Error Checking: CRC
    the communication is passed for only SLC5/03 and i can't communicate with micrologix1000.
    Notes :
    ALL the Devices is Powered UP
    My Questions are:
    1- Why this bad communication happened ?and how i overcome this problem?
    2-What the right configuration of the Rslinx that i can communicte with all Devices
    (micrologix1000 and SLC 5/03)

    راجع الكتيب الخاص بكل cpu مع استخدام الكابل و ال adapter الخاص بذلك مع العلم ان الوصلة التى استخدمتها لا تصلح مع الجميع


    0 Not allowed!